Belden Multi-Conductor – DataBus® ISA/SP-50 FOUNDATION Fieldbus or PROFIBUS Cable

Part #: 3076F 0031000

1 pair 18 AWG stranded (7x26) tinned copper conductors, polyolefin insulation, polyolefin filler, Beldfoil® shield (100% coverage), tinned copper drain wire, binder, PVC jacket. Fieldbus Foundation Registered Product.
  • Overview
  • Specifications
  • Overview
1 pair 18 AWG stranded (7x26) tinned copper conductors, polyolefin insulation, polyolefin filler, Beldfoil® shield (100% coverage), tinned copper drain wire, binder, PVC jacket. Fieldbus Foundation Registered Product.
  • Specifications
Physical Characteristics (Overall)
# Pairs1
AWG18
Stranding7x26
Conductor MaterialTC - Tinned Copper
Dia. (mm)1.168
Total Number of Conductors:2
Insulation MaterialPO - Polyolefin
Outer Shield Trade NameBeldfoil®
TypeTape
Outer Shield MaterialAluminum Foil-Polyester Tape
Coverage (%)100
AWG20
Stranding7x28
Drain Wire Conductor MaterialTC - Tinned Copper
Outer Jacket MaterialPVC - Polyvinyl Chloride
Nom. Dia. (mm)7.112
Overall Cabling Fillers:Polypropylene
Length (mm)57.150
Twists (twist/m)17.3893
Mechanical Characteristics (Overall)
Operating Temperature Range:-40°C To +105°C
UL Temperature Rating:105°C
Bulk Cable Weight:56.552 Kg/Km
Max. Recommended Pulling Tension:266.892 N
Min. Bend Radius/Minor Axis:63.500 mm
Applicable Specifications and Agency Compliance (Overall)
NEC/(UL) Specification:CMR, PLTC-ER
NEC Articles:725, 727, 800
CEC/C(UL) Specification:CMG
EU Directive 2011/65/EU (ROHS II):Yes
EU CE Mark:Yes
EU Directive 2000/53/EC (ELV):Yes
EU Directive 2002/95/EC (RoHS):Yes
EU RoHS Compliance Date (mm/dd/yyyy):01/01/2004
EU Directive 2002/96/EC (WEEE):Yes
EU Directive 2003/11/EC (BFR):Yes
CA Prop 65 (CJ for Wire & Cable):Yes
MII Order #39 (China RoHS):Yes
Other Specification:ITC-ER
UL Flame Test:UL1666 Riser
C(UL) Flame Test:FT4
IEEE Flame Test:1202, IEEE 383 Vertical Tray Flame Test (70,000 BTU)
Suitability - Indoor:Yes
Suitability - Outdoor:Yes
Suitability - Burial:Yes - UL
Sunlight Resistance:Yes
Oil Resistance:Yes
Plenum (Y/N):No
Electrical Characteristics (Overall)
Other Electrical Characteristic 1:Max Propagation Delay Change From 7.812 kHz to 39.06 kHz: 518 pS/ft
Other Electrical Characteristic 2:31.25 KBits/sec
Notes (Overall)
Notes:Fieldbus: Orange jacket. Profibus PA: Intrinsically Safe Blue jacket. Jacket diametre tolerance: +/- .010